International Structural Fire Protections
Materials
PAGE INDEX:
IMO FIRE TEST PROCEDURE CODE (IMO RESOLUTION
MSC.61(67))
To facilitate the use of IMO fire tests for fire protection materials,
IMO has incorporated these into a code, called the Fire Test Procedures
(FTP) Code. In addition to the IMO fire tests, the FTP Code contains
pass/fail criteria as well as additional requirements. The FTP Code
criteria must therefore be applied rather than the criteria in the
individual IMO resolutions or ISO standards. The FTP Code has been
incorporated into SOLAS as a mandatory instrument.
A significant addition to the FTP Code is the requirement for follow-up
inspections at the manufacturer's plant by an acceptable third party.
The FTP Code is divided into parts, each dealing with a specific set of
performance criteria as follows:
- Part 1 - Noncombustibility test
- Part 2 - Smoke and toxicity test
- Part 3 - Test for "A" and "B" Class divisions
- Part 4 - Test for fire control systems
- Part 5 - Test for surface flammability
- Part 6 - Test for primary deck coverings
- Part 7 - Test for vertically supported textiles and films
- Part 8 - Test for upholstered furniture
- Part 9 - Test for bedding components
To enable approving materials as meeting the above IMO criteria, and to
avoid confusion concerning the applicable pass/fail criteria, the Coast
Guard is establishing new material approval categories as listed below.
Most of the new approval category numbers have been selected to
correspond to the CFR approval categories. The exception is that the
IMO categories have the number "1" after the decimal point instead of
"0" (Example: for noncombustible materials the CFR approval category is
164.009, and for the IMO category the number is 164.109).
For materials or devices which had been approved on a
vessel-by-vessel basis under the CFR and for which no current approval
category
exists (doors, windows, penetration seal, and dampers), new approval
categories have been assigned as per the
Approval Guidance table below.
APPROVAL GUIDANCE
DECK ASSEMBLIES (A-60) (SOLAS)
APPROVAL CATEGORY: 164.105
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires typical bulkhead and deck prototypes to be tested in
accordance with the FTP Code to ensure that their construction meets
the requirements for A-Class divisions. All A-Class divisions must meet
the A-60 test standard. The FTP Code requires that all structural
insulation materials must be tested for non-combustibility under Annex
1, Part 1 and then tested for fire resistance under Annex 1, Part
3. This approval category is intended to cover insulation
systems that are installed above the steel deck plating. This
method of insulation is usually intended to provide a greater deal of
noise and vibration reduction for the passengers and crew. Deck
construction where the insulation is installed on the bottom side of
the deck is discussed in approval category 164.107.
Materials satisfying the noncombustibility criteria of Annex 1, Part 1
are considered to satisfy the surface flammability and smoke and
toxicity testing requirements for primary deck coverings (Annex 1, Part
2 and Part 6). A copy of the manufacturer's joint detailed and
typical installation instructions will become part of the approval.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL
PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
PRIMARY DECK COVERINGS (SOLAS)
APPROVAL CATEGORY:
164.106
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires primary deck coverings to be tested in accordance with
the FTP Code to ensure that they do not generate smoke or toxic or
explosive hazards at elevated temperatures. The FTP Code requires
all primary deck covering materials to be tested to the flame spread
criteria of Annex 1, Part 6 and the smoke density and toxicity criteria
of Annex 1, Part 2. The non-combustibility requirements of Annex
1, Part 1 do not apply.
Primary Deck Coverings vs. Floor
Coverings
The FTP Code defines primary deck covering as the first layer of floor
construction that is applied directly on top of the deck plating and is
inclusive of any primary coat, anti-corrosive compound or adhesive
which is necessary to provide protection or adhesion to the deck
plating. This category has no counterpart in the CFR. All
materials located above the primary deck covering are considered "floor
coverings" which are discussed under approval category 164.117.
Floor coverings are the layers placed on top of the primary deck
covering.
Primary deck coverings are generally installed to provide a level
surface for the application of the exposed floor covering.
Primary deck coverings that are intended only for installation beneath
a floor covering are tested on a steel substrate while floor coverings
are tested on the standard calcium silicate board referenced in IMO
Res. A.653(16).
Approved primary deck coverings may be used as floor coverings without
additional testing. As noted in paragraph 5.2 of Annex 2 of the
FTP Code, primary deck coverings that have been tested to Part 6 are
considered to also comply with the requirements of Part 5.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
STRUCTURAL INSULATION (A-60) (SOLAS)
APPROVAL CATEGORY: 164.107
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires typical bulkhead and deck prototypes to be tested in
accordance with the FTP Code to ensure that their construction meets
the requirements for A-Class divisions. The FTP Code requires
that all structural insulation materials must be tested for
noncombustibility under Annex 1, Part 1 and then tested for fire
resistance under Annex 1, Part 3. The FTP Code requires
structural insulations to be tested in the orientation in which the
material will be installed. Because of this, two tests are
required, one each in the vertical and horizontal orientations.
In the vertical test, the insulation is mounted on a stiffened 4-mm
thick steel core plate that is positioned in the furnace with the
insulation and stiffeners on the outside or unexposed side, while the
deck test specimen must have the insulation and stiffeners installed
below the steel deck plating and exposed to the furnace. The top
surface of the steel deck plating is normally left bare during the
test. If the test is to qualify aluminum construction, the test
specimen should include the primary deck coverings and floor finishes
that the manufacturer specifies, as they will affect the rate of heat
loss on the unexposed side of the assembly and could cause premature
structural failure of the aluminum core. The FTP Code requires
that the structural insulation must maintain the aluminum core plate
temperature below 200ºC above ambient temperature during the
test. Alternatively, aluminum decks may be tested with a bare top
side surface. If the underside insulation is capable of limiting
the core temperature to 150ºC, approval will be granted for the
use of any deck coverings.
Insulation materials must be tested at a density that is representative
of the manufactured product. Insulation densities will normally
fluctuate due to slight variations in production. Type approval
is therefore based on testing the insulation at the manufacturer’s
stated nominal density. The production density must be within
± 10 % of the nominal density. If the material is produced
at densities outside of this range, then two tests should be conducted
at the minimum and maximum nominal density, and all densities within
that range will be approved without further testing.
The figures in
NVIC 9-97
showing
A-60, A-30, and A-15 deck and bulkhead
constructions using combinations of materials do not apply to materials
tested to the FTP Code.
Normally, all structural insulations are tested in the thickness
necessary to achieve an A-60 approval. If a manufacturer requests
a separate approval for an A-30 or A-15 rating, additional testing must
be performed to determine the required thickness of insulation.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (G-MSE-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
BULKHEADS (B-0 & B-15) (SOLAS)
APPROVAL CATEGORY:
164.108 .
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires prototypes of typical bulkhead panel systems to be
tested in accordance with the FTP Code to ensure that their
construction meets the requirements for B-Class divisions. The
FTP Code requires all bulkhead panel materials to be tested for
noncombustibility under Annex 1, Part 1 except that adhesives used in
the panel construction may have low flame spread characteristics when
tested to Part 5 of the FTP Code rather than meeting non-combustibility
criteria. The panels are then tested for fire resistance under Annex 1,
Part 3. The FTP Code, Annex 1, Part 3 requires bulkhead panels to
be tested in accordance with IMO Res. A.754(18) for approval as B-0 or
B-15 divisions. The FTP Code acceptance criteria references B-30
approvals, however, there are no requirements in SOLAS for such a
bulkhead qualification. The Coast Guard does not, therefore,
recognize such a designation. Panels that pass the test for 30
minutes are approved as either B-0 or B-15 rated materials. If
the test is run for a 60 minute period, the bulkhead panel system may
be used as a component of A-Class construction, provided that the test
is conducted with a steel core plate as part of the test
assembly. To receive an unrestricted approval, two separate tests
must be conducted; one test with the bulkhead panel facing the fire and
one test with the steel core facing the fire. The tested distance
between the steel core and the panels is the minimum permitted in
actual installations. If approval of the panel system is to be
limited to B-0 or B-15 Class only, the fire test does not include a
steel bulkhead. If the panel system includes internal passages
for electric cables or light switches, samples of such panels must be
included in the test assembly.
Non symmetrical panel systems must be installed in the test furnace
with
the side giving the inferior performance exposed to the fire. If
a determination of which side of the panel this is cannot be easily
made from a review of the manufacturer's drawings, the panels must be
tested in each orientation.
Manufacturers of approved bulkhead panels are required to submit
drawings with typical joiner details as a required part of the
approval. The panels must be installed in accordance with the
manufacturer's typical installation drawings
Testing is conducted on panels without decorative surface finishes or
paints. Decorative surface finishes are approved separately under
Parts 2 and 5 of Annex 1 of the FTP Code.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required drawings and installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
NONCOMBUSTIBLE MATERIALS (SOLAS)
APPROVAL CATEGORY: 164.109
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires noncombustible materials to be tested in accordance with
the FTP Code to ensure that they do not burn or give off flammable
vapors in sufficient quantity for self-ignition when heated to
approximately 750ºC. The IMO FTP Code requires
noncombustible materials to be tested in accordance with ISO 1182-1990
using the acceptance criteria listed in Annex 1, Part 1 of the FTP
Code. These requirements are the same as IMO Res. A.799(18), which was
adopted after publication of the FTP Code. The use of
noncombustible materials
is a basic functional requirement of SOLAS for most material
approvals. Non-combustible materials may be used anywhere in
vessel construction without limitation.
The non-combustibility test is a severe heat exposure where five small
samples of the material are inserted into a tubular electric furnace
maintained at 750ºC. Materials approved under this category
to date are solid inorganic materials containing only small amounts of
organic binder. The samples must be selected at different
locations in a production run to ensure that they are representative of
the typical product.
To be considered non-combustible, the average performance of the
samples must not exceed any of the criteria shown below:
* a furnace temperature rise of 30 degrees C;
* a sample surface temperature rise of 30 degrees C;
* a duration of flaming of 10 seconds
* a weight loss of 50 percent.
The temperature rise criteria are determined as the difference between
the maximum temperature and the final temperature. This differs
from the procedure in 46 CFR 164.009 where the temperature rise is the
difference between the initial stabilization temperature and the
maximum temperature.
Some specific materials such as steel or glass is known to be
inherently noncombustible based on their composition, and may be used
in merchant vessel construction wherever noncombustible materials are
required. These materials do not need to be tested and do not
receive certificates of approval. A list of these materials is
contained in Annex 2 of the FTP Code. For a product to be
accepted as a noncombustible material without testing, the manufacturer
must certify that the product consists of only the materials listed in
Annex 2. All other materials must be tested.
Non-combustible C-Class Ceilings and
Bulkheads
The Coast Guard is now issuing type approvals for composite panel
construction intended for use as C-Class divisions, based on a recent
decision of the IMO Fire Protection Sub-Committee to allow the use of
adhesives with low flame spread characteristics as a component of
C-Class construction.
These type panels are generally aluminum honeycomb construction.
Manufacturers have two options for a C-Class type approval.
Representative samples of the panel may be cut and tested in accordance
with Annex 1, Part 1 for non-combustibility. The alternative
approach is to use only inherently noncombustible aluminum or steel
components that are held together with an adhesive that has been tested
under Annex 1, Part 5 for surface flammability. The Follow Up
Testing examines the adhesive application rate of the panel.
Acoustic and Thermal Insulation
SOLAS contains no performance requirements for acoustic and thermal
insulation. However, all insulation materials must be
non-combustible as detailed in SOLAS regulation II-2/5.3.
Combustible insulation is permitted in limited applications for cold
service piping if it is tested for surface flammability. This is
further discussed under approval category 164.143.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
CONTINUOUS CEILINGS (B-0 AND B-15) (SOLAS)
APPROVAL CATEGORY:
164.110.
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires prototypes of typical continuous ceiling panel systems
to be tested in accordance with the FTP Code to ensure that their
construction meets the requirements for B-Class divisions. The
FTP Code requires all ceiling panel materials to be tested for
non-combustibility under Annex 1, Part 1 except that adhesives used in
the panel construction may have low flame spread characteristics when
tested to Part 5 of the FTP Code rather than meeting non-combustibility
criteria. The panels are then tested for fire resistance under
Annex 1, Part 3, Appendix 2. Decorative surface finishes must be
tested separately under Parts 2 and 5 of the FTP Code.
The ceiling test procedure differs from the standard deck test
protocol, because the FTP Code requires the ceiling to be mounted in a
horizontal furnace on top of simulated bulkheads at least 150 mm high
to evaluate the proposed bulkhead/ceiling joint. If the ceiling
is intended to include lighting fixtures, ventilation system hardware
or electrical fittings, a second test must be conducted with
representative samples of these devices installed in the test specimen.
Continuous ceilings may also be used as a component in A-60 deck
construction when certain criteria are met. The fire test is normally
conducted with the ceiling suspended below a steel deck in accordance
with the manufacturer's instructions. The distance between the
steel plate simulating a steel deck in the test furnace and the
continuous ceiling below is considered to be the minimum separation
distance for actual shipboard installations. Temperature
measurements are made on top of the ceiling to determine compliance
with B-15 criteria and on top of the steel deck to determine compliance
with A-60 insulation criteria.
Each approval for a continuous ceiling is an approval of a specific
design. Extrapolation of the data for application to other designs is
not acceptable. Additional ceiling designs require additional
fire tests.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Typical installation details showing dimensions, suspension
system hardware and required joint details, based on the fire tests
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
DRAPERIES, CURTAINS & OTHER SUSPENDED
TEXTILES
APPROVAL CATEGORY:
164.111.
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires draperies, curtains and other suspended textiles used in
rooms containing furniture and furnishings of restricted fire risk
(Type 6 and some Type 7 spaces on passenger ships) to have qualities of
resistance to the propagation of flame not inferior to those of wool
having a mass of 0.8 kg/m2. This can be shown by testing in
accordance with the criteria in Annex 1, Part 7 of the FTP Code.
It is not necessary to conduct separate fire tests for different colors
of the same material.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
INTERIOR FINISH (BULKHEAD AND CEILING
FINISHES) (SOLAS)
APPROVAL CATEGORY: 164.112
APPROVAL GUIDANCE & INFORMATION:
SOLAS
permits the use of combustible materials for facings, moldings,
decorations and veneers if they comply with the criteria in regulation
II-2/5. Combustible materials used as exposed surfaces in
corridors and stairways and on bulkheads and ceilings in passenger ship
accommodation, service and control areas are required to have low flame
spread characteristics. This approval category includes only
bulkhead and ceiling finishes. Floor coverings are discussed under
164.117, below. The IMO FTP Code requires these materials to be
tested to the surface flammability test in Annex 1, Part 5, and the
smoke density and toxicity criteria of Annex 1, Part 2. The Part
5 testing is conducted first because materials with very low heat
release rates are accepted as complying with the smoke and toxicity
criteria in Part 2 without the need for further testing. It is
not necessary to conduct separate fire tests for different colors or
surface patterns of the same materials. If a manufacturer
produces an interior finish material at different thicknesses, only the
maximum thickness must be tested. The approval will permit the
use of all thicknesses up to the maximum.
The Part 2 smoke and toxicity tests are based on the ISO 5659:1994,
part 2 smoke chamber, but the acceptance criteria have been modified by
the FTP Code. SOLAS also requires exposed finishes to have a
calorific value not exceeding 45 MJ/m2 when tested in accordance with
ISO 1716 (oxygen bomb) test. The Coast Guard applies this
criterion to finishes which exceed 2 mm in thickness.
Any adhesives used in applying the finish must be part of the fire
test, and the manufacturer of the adhesive will be specified on the
certificate of approval issued for the finish. Other adhesives
may not be substituted without repeating the fire test using the
substitute adhesive.
Approved interior finishes may be applied as an exposed surface on any
approved bulkhead panels, ceilings and noncombustible substrates
without additional testing. The application of approved interior
finishes to other construction materials does not require Coast Guard
review, but must be done in accordance with the finish manufacturers
instructions.
SOLAS requires paints on exposed interior surfaces to meet the smoke
density and toxicity criteria of Annex 1, Part 2 of the FTP Code and
the surface flammability criteria of Annex 1, Part 5. Paint
manufacturers may test their paints to Part 5, and if the heat release
rates meet the criteria of paragraph 2.2 of Annex 2 of the FTP Code, no
further smoke and toxicity testing is necessary.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT
(MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
FLOOR FINISH (SOLAS)
APPROVAL CATEGORY: 164.117
APPROVAL GUIDANCE & INFORMATION:
SOLAS
permits the use of combustible materials for floor coverings if
they comply with the criteria in regulation II-2/5. Combustible
materials used as floor coverings in corridors, stairways and in rooms
containing furniture and furnishings of restricted fire risk (Type 6
and some Type 7 spaces on passenger ships) are required to have
low flame spread characteristics. The IMO FTP Code requires these
materials to be tested to the surface flammability test in Annex 1,
Part 5, and the smoke density and toxicity criteria of Annex 1, Part
2. The Part 5 testing is conducted first because materials with
very low heat release rates are accepted as complying with the smoke
and toxicity criteria in Part 2 without the need for further
testing. It is not necessary to conduct separate fire tests for
different colors or surface patterns of the same materials.
This approval category includes typical floor finishes such as vinyl
tiles and carpet. SOLAS considers floor coverings as the exposed
floor surface. Any materials installed beneath floor coverings
are considered primary deck coverings, which are approved under
category 164.106. If a floor covering consists of multi-layer
construction, testing may be required on the combination of layers or
each layer separately. The Coast Guard should be consulted prior
to testing to determine the necessary procedure. Floor coverings
are tested on a representative substrate or the standard calcium
silicate board referenced in IMO Res. A.653(16). The floor
covering may be mechanically fastened to the substrate or secured with
an adhesive. Any adhesives used are part of the fire test and the
application rate and manufacturer of the adhesive are referenced on the
type approval certificate.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT (MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place.
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
FIRE DOORS
APPROVAL CATEGORY: 164.136
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires fire doors in A-Class and B-Class bulkheads to provide
equivalent fire resistance to that of the bulkhead in which the doors
are installed. The FTP Code requires that all materials used in
the construction of fire doors must be tested for noncombustibility
under Annex 1, Part1 and then tested for fire resistance under Annex 1,
Part 3. Adhesives used in the construction of fire doors need not
be noncombustible, but they must be tested for low flame spread
characteristics under Annex 1, Part 5 and should be included in the
approved door’s follow-up program.
The maximum size door for which approval is requested must be
tested. If the required door size is larger than the test furnace
can accommodate, test the largest size possible. Fire doors may
be constructed of steel, galvanized steel or stainless steel.
Type approval will be issued for all three materials based on a single
fire test. The fire door frame may be either bolted or welded in
the test bulkhead. Doors that are tested with a bolted frame will
be approved for shipboard installation using either method. Doors
that are welded to the test bulkhead must be welded on the ship.
Doors must be mounted in the test bulkhead with the side expected to
give inferior performance exposed to the fire. Swinging doors
must be oriented in the test bulkhead to swing away from the
furnace. When it may not be possible to judge which side should
be tested such as for sliding doors, both sides of the bulkhead must be
tested. Prior to running the test, the U.S. Coast Guard should be
contacted to determine the recommended arrangements.
Doors may be tested with an integral window. Hose stream, thermal
radiation and temperature rise testing requirements for the glazing are
applicable as follows:
Window
Dimension |
Door Fire
Rating |
Hose Stream
Test Required? |
Heat Flux
Test Required? |
Temperature Rise
Test Required? |
| ≤ 645 cm2
|
A-Class |
None |
None |
None |
| ≥ 645
cm2
|
A-Class |
Yes |
Yes |
Yes |
| ≥ 645 cm2
|
A-0 |
Yes |
None |
None |
| ≤ 645 cm2
|
B-15 |
None |
None |
None |
| ≥ 645 cm2
|
B-15 |
None |
Yes |
Yes |
| Any dimension
|
B-0 |
None |
None |
None |
During the fire test, the surface temperatures on the unexposed side of
the door are measured by thermocouples fixed to the surface of the door
leaf. The thermocouples are located at the center of the door and
at the center of each of the four quarters of the door leaf. The
thermocouples are positioned at least 100 mm away from the edges of the
door and from any special features such as latches, hinges or door
knobs. If a temperature rise limitation is applicable to the
integral window, thermocouples should be attached to the unexposed
surface of the window as specified for a door leaf.
Doors should be tested with typical hinges, latches, hose ports,
electric strikes, viewers and other hardware that the manufacturer
intends to use for shipboard applications. The acceptance
criteria for door hardware requires only that the door remain closed
for the duration of the fire test and that openings in excess of that
permitted by the Code are not allowed to develop. None of the
door hardware is required to be functional after the fire test.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT (MRA) with windows not exceeding 645
cm2 in area.
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
WINDOWS
APPROVAL CATEGORY: 164.137
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires windows in A-Class and B-Class bulkheads and doors to
preserve the integrity requirements of the bulkhead or doors in which
they are fitted. The FTP Code requires windows to be tested for
fire resistance under Annex 1, Part 3. Windows must also meet the
thermal radiation test supplement to fire resistance, as outlined in
Appendix 1 of Part 3 of the FTP Code, and the hose stream test of
paragraph 5 of Appendix A.1 of Res. A.754(18). These tests are
not separate tests but are conducted during the normal fire resistance
test. These tests are labeled "optional" in the FTP Code, but are
required to obtain Coast Guard type approval. Windows less than
100 square inches do not require hose stream or thermal radiation tests.
Window fire tests are required to be conducted with the window
installed in a test bulkhead with the stiffeners and bulkhead
insulation exposed to the furnace. This configuration is intended
to represent exposure of the window to an interior fire scenario, as
would be expected on a passenger ship. For windows intended for
other applications, it may be necessary to test the sample with the
insulation and stiffeners on the unexposed side of the assembly.
This situation may exist for windows installed on tankers where the
fire exposure may to come from an exterior fire source. Approvals
are limited to the largest size windows tested. Unsymmetrical
window units that include multiple types of glazing, air gaps and
insulating materials must be tested in the orientation that they are
intended to be installed. In most cases this will require the
window to be mounted in the test bulkhead with the exterior glass layer
positioned away from the furnace.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Windows are
not
covered under the US / EC Mutual Recognition Agreement (MRA).
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
PENETRATION SEALS A-CLASS
APPROVAL CATEGORY: 164.138
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires penetrations of A-Class divisions for piping, electrical
cables and other shipboard systems to be tested to ensure that they do
not compromise the fire integrity of the penetrated barrier. Such
devices must be tested for their fire resistance in accordance with
Annex 1, Part 3 of the FTP Code and Appendices A.III and A.IV of
Resolution. A.754(18). Penetration seals are not required to be
constructed of noncombustible materials and they do not have to meet
surface flammability or smoke and toxicity criteria. The Code
allows this because penetration seals must have a degree of flexibility
to seal around the penetrating items and remain in place when subjected
to expected shipboard motions.
Fire rated penetration seals that must also be watertight are tested
separately for their watertight properties. The seals do not need
to be tested for water tightness after they have undergone fire
testing. The watertight test specimen should be the size
specified in the watertight testing procedures, and does not need to be
the same size as that fire tested. If a penetration seal has been
successfully tested for water tightness, the manufacturer may request
the type approval certificate to include information to that effect.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT (MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
DAMPERS
APPROVAL CATEGORY: 164.139
APPROVAL GUIDANCE & INFORMATION:
Automatic
fire dampers that are installed in A-Class divisions must be
tested for their fire resistance in accordance with Annex 1, Part 3 of
the FTP Code and Appendix A.II of Resolution. A.754 (18). Two
fire tests are required, one in a vertical furnace for bulkhead
penetrations and the other in a horizontal furnace for deck
penetrations. The test bulkhead is mounted in the furnace with
its stiffeners and insulation on the unexposed surface; the deck test
specimen is mounted with the insulation and stiffeners on the bottom or
exposed side. The FTP Code requires that penetrations must only
be installed in the top half of the test bulkhead to simulate actual
fire exposure conditions. However, the Coast Guard will accept
tests with penetrations that extend below the mid-height of the test
bulkhead if the laboratory adjusts the neutral plane of the furnace
below the level of the penetrating devices.
The minimum and maximum size dampers for which approval is requested
should be tested. Dampers are required to automatically
close, thus they must be tested with an installed operator.
Dampers that are tested with only a fusible link operator will be
limited to the use of only fusible links. If the manufacturer
wishes to use a variety of electrical or pneumatic operators they
should be included in the fire tests. Manufacturers need not test
every damper size and configuration with each operator. All types
of operators will be accepted if representative specimens of each are
included in the fire tests.
Fire dampers must be in the open position at the start of the test and
must close automatically. Manual closure of the dampers is not
acceptable. The ductwork connected to the dampers must be open
during the test.
For Coast Guard type approval, the penetrations must successfully pass
only the integrity criteria of Res. A.754(18). For installation
in A-Class divisions, the damper sleeve is required to be insulated
similar to the division penetrated.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT (MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans of the equipment that show typical installation
details for both bulkhead and deck configurations and the installation
instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
PENETRATION SEALS H-CLASS
APPROVAL CATEGORY: 164.140
APPROVAL GUIDANCE & INFORMATION:
H-class divisions are constructed of steel or other equivalent materials and are capable of preventing the passage of flame and smoke for two hours. In addition, they are classified as H-120, H-60 or H-0 depending on the time the assembly is capable of preventing the maximum temperature rise from exceeding 180°C. H-class divisions may be required on offshore facilities to separate accommodation areas, control stations, or vital equipment from the drill floor and other hazardous locations.
H-class prenetrations are evaluated using the test procedures and acceptance criteria in the FTP Code, Annex 1, Part 3, with the exception of the furnace time-temperature curve. The standard furnace heating curve is replaced with the hydrocarbon curve in the laboratory test furnace, which is intended to simulate the higher heat flux from a burning flammable liquids fire.
H-class penetrations are typically only installed in exterior boundaries. Because of this, their approvals are restricted for installation where the side of the penetration seal that was exposed to the test furnace is on the exterior side of the penetrated division. If the seal is tested with each side of the assembly exposed to the furnace separately, the approval will be unrestricted, i.e., the seal may be installed in the penetrated division with either side exposed to the weather.
If a seal assembly is intended to be used in both bulkhead and deck applications, it must undergo two separate approval tests, one in the vertical orientation and one in the horizontal orientation.
This item cannot be approved under the US/EC Mutual
Recognition Agreement (MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W. Stop 7126
Washington, DC 20593-7126
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
FIBER REINFORCED PLASTIC PIPES
APPROVAL CATEGORY: 164.141
APPROVAL GUIDANCE & INFORMATION:
See
POLICY FILE MEMORANDUM ON THE FIRE
PERFORMANCE REQUIREMENTS FOR
PLASTIC PIPE PER IMO RESOLUTION A.753(18)
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
LINKS: Alternate
fire endurance test.
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
BEDDING COMPONENTS
APPROVAL CATEGORY: 164.142
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires bedding components such as blankets, quilts, bedspreads,
pillows and mattresses used in rooms containing furniture and
furnishings of restricted fire risk (Type 6 and Type 7 public spaces on
passenger ships) to have qualities of resistance to the ignition and
propagation of flame as determined by testing in accordance with Annex
1, Part 9 of the FTP Code. This test is a small scale test
intended to assess the ignitability of bedding components when exposed
to a cigarette and lighted match. It is not necessary to conduct
separate fire tests for different colors of the same materials.
Box springs are not required to be tested, since their upper surface is
covered by other bedding components.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT (MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
UPHOLSTERED FURNITURE
APPROVAL CATEGORY: 164.144
APPROVAL GUIDANCE & INFORMATION:
SOLAS
requires upholstered furniture used in rooms containing furniture
and furnishings of restricted fire risk (Type 6 and some Type 7 public
spaces and in stairways on passenger ships) to have qualities of
resistance to the ignition and propagation of flame as determined by
testing in accordance with Annex 1, Part 8 of the FTP Code. This
test is a small scale test intended to assess the ignitability of
material combinations when exposed to a cigarette or lighted
match. The combination must be representative of the final
product. Individual components (such as fabric, foam, and
batting) can not be approved. It is not necessary to conduct
separate fire tests for different colors of the same furniture.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT (MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instruction
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
FIRE DOOR CONTROL SYSTEM (IMO)
APPROVAL CATEGORY: 164.146
APPROVAL GUIDANCE & INFORMATION:
SOLAS
regulation II-2/9.4 requires power operated fire doors in main
vertical zone bulkheads, galley boundaries and stairway enclosures to
be able to operate in case of fire. Testing of the door control
system must be performed in accordance with Annex 1, Part 4 of the FTP
Code to demonstrate that the door is operable for at least one hour at
temperatures up to 200ºC, and at higher temperatures, the control
system must disengage to keep the door in the closed position.
The test is conducted by mounting a scale model power operated door in
a standard test bulkhead. The furnace temperature is controlled
at 200ºC for 60 minutes during which time the door is opened and
closed every 5 minutes to demonstrate the control function. After
60 minutes, the furnace temperature is increased to the standard IMO
time temperature curve. The model door must remain closed until a
temperature of at least 945ºC is reached.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
This item can be approved under the
US/EC MUTUAL
RECOGNITION AGREEMENT (MRA).
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
FIRE RESTRICTING MATERIALS FOR HIGH SPEED
CRAFT
APPROVAL CATEGORY: 164.201
APPROVAL GUIDANCE & INFORMATION:
The
High Speed Craft (HSC) Code defines fire-restricting materials as
having properties complying with the Fire Test Procedures (FTP)
Code. The FTP Code Annex I, Part 10 is the test standard for
fire-restricting materials on high-speed craft. Part 10 was
approved by Resolution MSC/101 (73), and does not appear in the current
print edition of the FTP Code. The HSC Code regulation 7.4
requires the hull, superstructure, structural bulkheads, decks,
deck houses, and pillars be constructed of approved non-combustible
materials with adequate structural properties, or fire-restricting
materials that comply with the Fire Test Procedures (FTP) Code.
Fire restricting materials including surface materials on bulkheads,
wall and ceiling linings including their supporting structure,
furniture and other structural or interior components shall be tested
and evaluated in accordance with the fire test procedures specified in
IMO Resolution MSC.40(64) as amended by IMO Resolution
MSC.90(71). The tests are performed according to the standard ISO
9705 (Room/Corner Test) and the criteria that must be met are located
in IMO Resolutions.
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
FIRE-RESISTING DIVISIONS FOR HIGH SPEED CRAFT
APPROVAL CATEGORY: 164.207
APPROVAL GUIDANCE & INFORMATION:
The
HSC Code regulation 7.4.2 requires bulkheads, decks, ceilings,
linings and doors to have fire resisting properties.
Fire-resisting divisions must comply with the FTP Code Annex I, Part 11
(Part 11 was approved after the FTP Code was printed). Part 11
requires fire resisting divisions to be tested and evaluated in
accordance with the fire test procedures specified in IMO Resolution
MSC.45(65).
The Coast Guard does not test materials or systems for approval but
rather specifies the required test methods and minimum performance
criteria for approval. The testing must be performed on the
product by a Coast Guard Accepted Independent Laboratory.
The following are additional requirements for materials approved for
use in fire-resisting divisions:
- Materials must be non-combustible or fire-restricting as verified
in accordance with Part 1 or Part 10 of Annex 1 of the FTP Code.
- FTP Code Annex I, Part 3 is applicable to certain constructions
such as windows, fire dampers, pipe penetrations and cable transits.
- FTP Code Annex, I Part 4 is applicable where a control system of
fire doors is required to be able to operate in case of fire.
- Combustible veneers are allowed on fire-resisting divisions in
conjunction with non-combustible substrates, the low flame spread
characteristics of such veneers will be verified in accordance with FTP
Code Annex I, Part 5.
SUBMITTAL PACKAGE: Please
submit the follow information in the Submittal Package:
- A letter requesting Coast Guard Type Approval of the equipment.
- A test report from the Accepted Independent Laboratory showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Laboratory is in place
- Required drawings/plans of the equipment
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has approved by this office it will received Coast
Guard Type Approval and a Certificate of Approval (COA). The COA
will be issued for 5 years and will remain valid during that time
period if product meets the testing of the Quality Control Program.