Domestic Structural Fire Protection Material
Regulations
PAGE INDEX:
Title 46 of the Code of Federal Regulations (CFR) requires certain
portions of U.S. flag commercial vessels to be constructed of Coast
Guard approved materials. The fire test methods contained therein
are based primarily on ASTM fire test standards. The approval
number on the certificate will correspond to the respective approval
category in the CFR, such as 164.007/XX/0 for structural insulation
approved to 46 CFR 164.007.
APPROVAL GUIDANCE: DOMESTIC
FLAME SAFETY LAMPS FOR MERCHANT VESSELS
SUBPART NUMBER: 160.016
APPROVAL GUIDANCE & INFORMATION:
Coast Guard regulations require the carriage of approved flame safety
lamps as part of fire man’s outfits. Flame safety lamps were type
approved previously under 46 CFR 160.016, if they met Military
Specification MIL L-1204, but flame safety Lamps are no longer being
made.
In its place the Coast Guard will accept combination combustible
gas/oxygen depletion meters which have been approved as intrinsically
safe by Factory Mutual Corp. (FM) or so Listed by Underwiters
Laboratories, Inc. (UL).
DECK ASSEMBLIES
SUBPART NUMBER: 164.005
APPROVAL GUIDANCE &
INFORMATION: Traditionally, deck coverings on U. S.
vessels have been the the oxychloride cements (magnesites), topped with
tile or other overlays for finishing purposes. The traditional approval
category, 46 CFR 164.006, is oriented toward the testing of A-60
insulation materials applied on top of a steel deck rather than
prefabricated insulation systems such as floating floors. To
accommodate floating floors providing A-60 deck protection, we have
established under approval series 164.005, a separate category for deck
assemblies (although there is no corresponding text in the CFRs apply
criteria taken from IMO Fire Resistance Tests). Approval requirements
include meeting noncombustibility criteria, as well as meeting the
temperature limitation, and flame and smoke penetration criteria for
A-60 boundaries as specified in the CFRs. The Coast Guard does
not test materials or systems for approval but rather specifies the
required test methods and minimum performance criteria for
approval. The testing must be performed on the product by a Coast
Guard Accepted Independent Testing Laboratory.
SUBMITTAL PACKAGE: Please
submit the following information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Testing Laboratory
showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place.
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
DECK COVERINGS (A-60)
SUBPART NUMBER: 164.006
APPROVAL GUIDANCE & INFORMATION:
Deck coverings are tested for compliance with 46 CFR 164.006, entitled
"Deck Coverings for Merchant Vessels." This specification is applicable
to decks where a fire resistance rating is required, such as A-15,
A-30, or A-60, and the fire exposure is expected to be from below the
deck. Materials approved under this specification have been mixtures
such as magnesium oxychloride cements, prepared at the job site, which
are held to the steel deck with welded steel clips or an adhesive
material. This test does not require the materials to be
noncombustible. Instead, it specifies limits on the organic carbon
content, fire resistance, temperature transmission, and smoke density.
The test is conducted to meet A-60 criteria. The approval for A-60
applications is limited to the thickness tested as a minimum. Based on
the test for A-60, a reduced thickness of the material may be applied
to meet A-30 and A-15 criteria. The applicable details are contained in
NVIC 9-97. The Coast Guard does not test materials or systems for
approval but rather specifies the required test methods and minimum
performance criteria for approval. The testing must be performed
on the product by a Coast Guard Accepted Independent Testing Laboratory.
SUBMITTAL PACKAGE: Please
submit the following information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Testing Laboratory
showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
STRUCTURAL INSULATION
SUBPART NUMBER: 164.007
APPROVAL GUIDANCE & INFORMATION:
The approval specification for structural insulation is 46 CFR 164.007.
This specification also requires compliance with the noncombustibility
criteria of 46 CFR 164.009, resulting in separate fire tests for
noncombustibility, and for fire resistance. Each insulation material is
tested in the minimum thickness specified by the manufacturer,
utilizing the method of installation recommended by the manufacturer.
Typically, the insulation material is attached to a steel bulkhead with
welded pins and speed clips. A joint or seam must be included in the
test assembly. A set of typical installation drawings must be supplied
to the testing laboratory to aid in the construction of the test
sample. The drawing is to be representative of the expected
installation of the insulation on ships.
The test is conducted to meet A-60 criteria. The approval for A-60
applications is limited to the thickness tested as a minimum. Based on
the test for A-60, a reduced thickness of the material may be applied
to meet A-30 and A-15 criteria. The applicable details are contained in
NVIC 9-97.
The test specification states that the sample must be tested with the
insulation facing the furnace fire, but the insulation may then be
installed on a ship on either side of a steel bulkhead or under a steel
deck. The Coast Guard does not test materials or systems for
approval but rather specifies the required test methods and minimum
performance criteria for approval. The testing must be performed
on the product by a Coast Guard Accepted Independent Testing Laboratory.
SUBMITTAL PACKAGE: Please
submit the following information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval of the
equipment.
- A test report from the Accepted Independent Testing Laboratory
showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place
- Required plans and a copy of the installation instructions.
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
BULKHEAD PANELS
SUBPART NUMBER: 164.008
APPROVAL GUIDANCE &
INFORMATION: The applicable requirements are contained in
specification 46 CFR 164.008. The latter requires the panels (including
any internal adhesive) to also meet the noncombustibility criteria of
46 CFR 164.009. The panels are installed in accordance with the
manufacturer’s recommended joiner construction details, which becomes a
required part of the approval of the panels.
46 CFR 164.008 does not require the use of steel bulkheads as part of
the fire resistance test. Instead, the panels are tested without steel
bulkheads for B-0 or B-15 classifications. Panels which successfully
meet B-15 criteria and the fire resistance criteria for one hour may
then be used as a component (along with other approved materials and
air spaces) in A-60 bulkhead construction in accordance with the
construction arrangements shown in NVIC 9-97. The Coast Guard
does not test materials or systems for approval but rather specifies
the required test methods and minimum performance criteria for
approval. The testing must be performed on the product by a Coast
Guard Accepted Independent Testing Laboratory.
If panels are to contain internal passages for electric cables or light
switches, samples of such panels must included in the test assembly.
Testing is conducted on unfaced panels only. Any decorative surface
finishes must be approved separately under 46 CFR 164.012.
A set of joint detail and typical joiner installation drawings must be
provided before the test as well as a drawing of the test specimen as
it is to be installed in the test furnace. The set of typical drawings
will be stamped "Approved" and will become a part of the approval data.
SUBMITTAL PACKAGE: Please
submit the following information in the Submittal Package:
- A letter requesting Coast Guard Type Approval of the equipment.
- A test report from the Accepted Independent Testing Laboratory
showing
compliance of the product or equipment with the applicable standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place
- Required drawings/plans of the equipment
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has approved by this office it will received Coast
Guard Type Approval and a Certificate of Approval (COA). The COA
will be issued for 5 years and will remain valid during that time
period if product meets the testing of the Quality Control Program.
NONCOMBUSTIBLE MATERIALS
SUBPART NUMBER: 164.009
APPROVAL GUIDANCE & INFORMATION:
This is the basic specification for most material approvals.
Noncombustible materials may be used anywhere in vessel construction
without limitation. Approval certificates are issued under this
category after samples of the material successfully meet the fire test
criteria. This requires inserting material samples into a small
electric furnace maintained at 750 degrees C. To be considered
noncombustible, the average of the samples must not exceed each of the
following: a furnace temperature rise of 50 degrees C, a sample surface
rise of 50 degrees C, a duration of flaming of 10 seconds, and a weight
loss of 50 percent. Materials approved under this category to date are
solid inorganic materials containing only small amounts of organic
binder.
Some specific materials are known to be noncombustible based on their
composition, and may be used in merchant vessels construction wherever
noncombustible materials are required. These materials are not tested
and do not receive certificates of approval. A list of these materials
is contained in 46 CFR 164.009-3. For a product to be accepted as a
noncombustible material not requiring tests, its manufacturer must
certify that the product consists only of the materials listed in
164.009-3. All other materials must be tested. The Coast Guard
does not test materials or systems for approval but rather specifies
the required test methods and minimum performance criteria for
approval. The testing must be performed on the product by a Coast
Guard Accepted Independent Testing Laboratory.
SUBMITTAL PACKAGE: Please
submit the following information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Testing Laboratory
showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place
- Required plans and a copy of the installation instruction
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
CONTINUOUS CEILINGS
SUBPART NUMBER: 164.010 .
APPROVAL GUIDANCE &
INFORMATION: The Code of Federal Regulations does not
require continuous (B-0 or B-15) ceiling systems, since B-0 and B-15
bulkheads are installed deck to deck to provide a continuous fire
barrier. However, since the SOLAS treaty recognizes continuous ceilings
in lieu of installing bulkheads deck to deck, the Coast Guard has
established an approval category for continuous ceilings, and assigned
it approval category 164.010. Since the CFRs contain no appropriate
approval criteria, the test procedure and acceptance criteria applied
were taken from IMO Resolution A.517(13).
Since they are part of a B-class partition, all ceiling materials, with
the exception of decorative surface finishes, must be noncombustible
per 46 CFR 164.009. Decorative surface finishes must be approved
separately under 46 CFR 164.012.
For ceilings which are intended to incorporate recessed light fixtures,
ventilation units (diffusers), access panels, and recessed light
switches, the test assembly must include a recessed light fixture
housing, a diffuser, an access panel and a light switch housing. A
separate test for ceilings incorporating accessories may be required if
the accessories are extensive.
Continuous ceilings may also be used to meet A-60 deck criteria when
certain conditions are met. In the latter case the fire test is
conducted with the ceiling suspended below a steel deck in accordance
with the manufacturer’s instructions. The distance between the steel
plate simulating a steel deck in the test furnace and the continuous
ceiling below is considered to be the minimum distance for actual
shipboard installation. Temperature measurements are made on top of the
ceiling to determine compliance with B-15 ceiling criteria and on top
of the steel deck to determine compliance with A-60 deck insulation
criteria.
Each approval for a continuous ceiling is an approval of a specific
design, as shown on the manufacturer’s approved joint detail and
typical joiner construction drawings. Extrapolations of the data for
application to other designs are not made. Additional ceiling designs
require additional fire tests. The construction and material
combinations shown in NVIC 9-97 for constructing A-60, A-30, and A-15
bulkheads and decks do not apply to continuous ceilings. The
Coast Guard does not test materials or systems for approval but rather
specifies the required test methods and minimum performance criteria
for approval. The testing must be performed on the product by a
Coast Guard Accepted Independent Testing Laboratory.
SUBMITTAL PACKAGE: Please submit the following information in the
Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Testing Laboratory
showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place
- Required plans and a copy of the installation instructions
Please send the Submittal Package and other related information to the
following address:
Commandant (G-MSE-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
INTERIOR FINISH
SUBPART NUMBER: 164.012
APPROVAL GUIDANCE &
INFORMATION: The U. S. Coast Guard approval category for
interior (decorative surface) finishes is 46 CFR 164.012. This
specification requires decorative bulkhead and ceiling facings and
coatings not exceeding 0.075 inches (1.9 mm) in thickness to meet low
flame spread and smoke values. Thicker materials must be
non-combustible. Any adhesives used in applying the finish must be part
of the fire test, and will be specified on the certificate of approval
issued for the finish. Other adhesives may not be substituted
without repeating the fire test using the substitute adhesive.
The test method is ASTM E-84, and the finish must have maximum flame
spread and smoke developed ratings of 20 and 10, respectively.
These finishes are for surface application to noncombustible substrates
only.
Approved interior finishes may then be applied as a surface finish to
any other approved non-combustible material, such as bulkhead panels
and ceilings, without requiring additional approvals. The process
of applying approved finishes to approved construction materials does
not require approval, but must be done in accordance with the finish
manufacturer’s instructions. The Coast Guard does not test
materials or systems for approval but rather specifies the required
test methods and minimum performance criteria for approval. The
testing must be performed on the product by a Coast Guard Accepted
Independent Testing Laboratory.
LINKS:
ASTM E-84 (
This link will take you to the website for
the ASTM.)
SUBMITTAL PACKAGE: Please
submit the following information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval.
- A test report from the Accepted Independent Testing Laboratory
showing
compliance with the above standard.
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place
- Required plans and a copy of the installation instruction
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.
FIBER REINFORCED PLASTIC GRATING & CABLE
TRAYS
SUBPART NUMBER: 164.040
APPROVAL GUIDANCE & INFORMATION:
See the Fiber Reinforced Plastic Grating link. The Coast Guard
does not test materials or systems for approval but rather specifies
the required test methods and minimum performance criteria for
approval. The testing must be performed on the product by a Coast
Guard Accepted Independent Testing Laboratory.
LINKS: FIBER REINFORCED
PLASTIC (FRP) GRATING
SUBMITTAL PACKAGE: Please
submit the following information in the Submittal Package:
- A cover letter requesting Coast Guard Type Approval
- A test report from the Accepted Independent Testing Laboratory
showing
compliance with the above standard
- Evidence that an acceptable follow-up factory inspection program
with the Accepted Independent Testing Laboratory is in place
- Required plans and a copy of the installation instruction
Please send the Submittal Package and other related information to the
following address:
Commandant (CG-ENG-4)
U.S. Coast Guard
2100 Second Street, S.W.
Washington, DC 20593-0001
Once the equipment has been approved by this office it will received
Coast Guard Type Approval and a Certificate of Approval (COA).
The COA will be issued for 5 years and will remain valid during that
time period if the product meets the testing of the Quality Control
Program.